T1 - Experimental Investigation of the Humidification Parameters in a Vertically Aligned Triple Pad Multistage Evaporative Cooler
AU - Salins, Sampath Suranjan
AU - Kumar, Shiva
AU - Kota Reddy, S. V.
AU - Ajith, Krishna
N1 - Publisher Copyright:
Copyright © 2022 by ASME.
PY - 2022/12
Y1 - 2022/12
N2 - The present work involves designing and fabricating the three-stage humidifier test rig where three Celdek 7090 packings are arranged vertically at equidistance, forming a multistage humidifier. Water flowrate and airflow rates are regulated to obtain required humidification under both single-pad and three-pad configurations. Output variables like the coefficient of performance, evaporation rate, cooling effect, cooling efficiency, and pressure drop are determined. Results indicated that three-stage packing gave high performance compared to the single stage. Changes in temperature, change in humidity, saturation efficiency, and coefficient of performance values are 6.5 °C, 44%, 80%, and 2.1, respectively, are the maximum values noticed for the multistage humidifier. The study indicated that with the increase in the rate of water flow, there is a rise in performance parameters till a water flowrate of 0.6 l per minute, and after this value, performance deteriorates. Even though multistage performs better than a single stage, as the number of stages increases, the stage-wise performance declines.
AB - The present work involves designing and fabricating the three-stage humidifier test rig where three Celdek 7090 packings are arranged vertically at equidistance, forming a multistage humidifier. Water flowrate and airflow rates are regulated to obtain required humidification under both single-pad and three-pad configurations. Output variables like the coefficient of performance, evaporation rate, cooling effect, cooling efficiency, and pressure drop are determined. Results indicated that three-stage packing gave high performance compared to the single stage. Changes in temperature, change in humidity, saturation efficiency, and coefficient of performance values are 6.5 °C, 44%, 80%, and 2.1, respectively, are the maximum values noticed for the multistage humidifier. The study indicated that with the increase in the rate of water flow, there is a rise in performance parameters till a water flowrate of 0.6 l per minute, and after this value, performance deteriorates. Even though multistage performs better than a single stage, as the number of stages increases, the stage-wise performance declines.
UR - http://www.scopus.com/inward/record.url?scp=85144401026&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85144401026&partnerID=8YFLogxK
U2 - 10.1115/1.4055262
DO - 10.1115/1.4055262
M3 - Article
AN - SCOPUS:85144401026
SN - 1948-5085
VL - 14
JO - Journal of Thermal Science and Engineering Applications
JF - Journal of Thermal Science and Engineering Applications
IS - 12
M1 - 121012
ER -