Abstract
The present work involves designing and fabricating the three-stage humidifier test rig where three Celdek 7090 packings are arranged vertically at equidistance, forming a multistage humidifier. Water flowrate and airflow rates are regulated to obtain required humidification under both single-pad and three-pad configurations. Output variables like the coefficient of performance, evaporation rate, cooling effect, cooling efficiency, and pressure drop are determined. Results indicated that three-stage packing gave high performance compared to the single stage. Changes in temperature, change in humidity, saturation efficiency, and coefficient of performance values are 6.5 °C, 44%, 80%, and 2.1, respectively, are the maximum values noticed for the multistage humidifier. The study indicated that with the increase in the rate of water flow, there is a rise in performance parameters till a water flowrate of 0.6 l per minute, and after this value, performance deteriorates. Even though multistage performs better than a single stage, as the number of stages increases, the stage-wise performance declines.
| Original language | English |
|---|---|
| Article number | 121012 |
| Journal | Journal of Thermal Science and Engineering Applications |
| Volume | 14 |
| Issue number | 12 |
| DOIs | |
| Publication status | Published - 12-2022 |
All Science Journal Classification (ASJC) codes
- General Materials Science
- Condensed Matter Physics
- General Engineering
- Fluid Flow and Transfer Processes
Fingerprint
Dive into the research topics of 'Experimental Investigation of the Humidification Parameters in a Vertically Aligned Triple Pad Multistage Evaporative Cooler'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver